Description
- Display Type: Digital Only
- Testing Voltage: Refer to the SPEC
- Dimensions: 133 mm x 187 mm x 250 mm
- Brand Name: FLUKE
- Measuring Range: Refer to the SPEC
- Operating Temperature: -10 to 50C
- DIY Supplies: ELECTRICAL
- Model Number: 1625-2
- Accuracy Class: Refer to the SPEC
For Fluke 1625-2 Kit – Advanced Geo Earth Ground Tester
The Fluke 1625-2 Kit, is a distinctive earth ground tester that can perform all four types of earth ground measurement. Specifically, the Fluke 1625 Kit tester is able to measure earth ground loop resistances using only clamps – called Stakeless testing. This method doesn’t require the use of earth ground stakes or the disconnection of ground rods.
Feature:
The Fluke 1625 Kit offers these advanced features:
Automatic Frequency Control (AFC) – identifies existing interference and chooses a measurement frequency to minimize its effect, providing a more accurate earth ground value
R* measurement – calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to-earth ground would see
Adjustable limits – for quick test result verification
4-pole earth ground measurement
4-pole soil resistivity testing
2-pole resistance measurement AC
2- and 4-pole resistance measurement DC
Selective testing, no disconnection of ground conductor (1 clamp)
Stakeless testing, quick ground loop testing (2 clamps)
Earth impedance measurement at 55 Hz
Automatic frequency control (AFC) (94, 105, 111, 128 Hz)
Measuring voltage switchable 20/48V
Programmable limits, settings
Continuity with buzzer
Specifications:
RA 3-pole Ground Resistance Measurement (IEC 1557-5) | |
Measuring voltage | Vm = 20/48 V AC |
Short circuit current | 250 mA AC |
Measure frequency | 94, 105, 111, 128Hz |
Resolution | 0.001 Ω to 100 Ω |
Measuring range | 0.001 Ω to 299.9 kΩ |
Intrinsic error | ± (2 % of rdg + 2 d) |
Operating error | ± (5 % of rdg + 5 d) |
RA 4-pole Ground Resistance Measurement (IEC 1557-5) | |
Measuring voltage | Vm = 20/48 V AC |
Short circuit current | 250 mA AC |
Measure frequency | 94, 105, 111, 128Hz |
Resolution | 0.001 Ω to 100 Ω |
Measuring range | 0.001 Ω to 299.9 kΩ |
Intrinsic error | ± (2 % of rdg + 2 d) |
Operating error | ± (5 % of rdg + 5 d) |
RA 3-pole Ground Resistance Measurement With Current Clamp | |
Measuring voltage | Vm = 20/48 V AC |
Short circuit current | 250 mA AC |
Measure frequency | 94, 105, 111, 128Hz |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.001 Ω to 29.99 kΩ |
Intrinsic error | ± (7 % of rdg + 2 d) |
Operating error | ± (10 % of rdg + 5 d) |
RA 4-pole Selective Ground Resistance Measurement With Current Clamp | |
Measuring voltage | Vm = 20/48 V AC |
Short circuit current | 250 mA AC |
Measure frequency | 94, 105, 111, 128Hz |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.001 Ω to 29.99 kΩ |
Intrinsic error | ± (7 % of rdg + 2 d) |
Operating error | ± (10 % of rdg + 5 d) |
Stakeless Ground Loop Measurement | |
Measuring voltage | Vm = 20/48 V ac |
Measure frequency | 94, 105, 111, 128Hz |
Noise current (Iext) | Max. Iext = 3 A |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.001 Ω to 29.99 kΩ |
Intrinsic error | ± (7 % of rdg + 2 d) |
Operating error | ± (10 % of rdg + 5 d) |
Environmental Specifications | |
Working temperature | -10 °C to +50 °C |
Operating temperature | 0 °C to +35 °C |
Nominal temperature | +18 °C to +28 °C |
Storage temperature | -30 °C to +60 °C |
Climatic class | C1 (IEC 654-1), -5 °C to + 45 °C, 5 % to 95 % RH |
Protection type | IP56 for case, IP40 for battery door according to EN 60529 |
Safety Specifications | |
Safety rating | CAT II, 300 V |
Mechanical And General Specifications | |
Display | 2999 Digit LCD – 7 segment liquid crystal display with special symbols and backlight |
Size | 133 mm x 187 mm x 250 mm |
Weight | 1.1 kg (including batteries) |
Warranty | Two years |
Battery life | Typical 3000 measurements (RE+RH ≤ 1 kΩ) |
Typical 6000 measurements (RE+RH ≤ 10 kΩ) |
Fluke 1625 Kit – Advanced Geo Earth Ground Tester :
- Fluke 1625 Tester
- 2 test leads
- 4 earth ground stakes
- 3 cable reels with wire (2-25 m, 1-50 m)
- 2 clamps (one inducing, one sensing)
- Batteries(not included )
- User’s manual
- Rugged carrying case
H.Q.S